-40%

UNO-PS/1AC/24DC/ 240W 24V DC 10A 240W power supply 2904372

$ 25.76

Availability: 100 in stock
  • Model: UNO-PS/1AC/24DC/ 240W
  • All returns accepted: ReturnsNotAccepted
  • Nominal Current Rating: 10 A
  • Condition: Pulled working from control panel
  • Brand: Phoenix Contact
  • MPN: 2904372
  • Country/Region of Manufacture: Germany
  • Output Voltage Rating (DC): 24 V

    Description

    Product Description
    UNO POWER power supplies - compact with basic functionality
    Thanks to their high power density, compact UNO POWER power supplies offer the ideal solution for loads up to 240 W, particularly in compact control boxes. The power supply units are available in various performance classes and overall widths. Their high degree of efficiency and low idling losses ensure a high level of energy efficiency.
    Dimensions
    Width
    45 mm
    Height
    130 mm
    Depth
    125 mm
    Installation distance right/left
    0 mm / 0 mm
    Installation distance top/bottom
    30 mm / 30 mm
    Back to top
    Ambient conditions
    Degree of protection
    IP20
    Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
    Ambient temperature (operation)
    -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
    Ambient temperature (start-up type tested)
    -25 °C
    Ambient temperature (storage/transport)
    -40 °C ... 85 °C
    Max. permissible relative humidity (operation)
    ≤ 95 % (at 25 °C, non-condensing)
    Climatic class
    3K3 (in acc. with EN 60721)
    Degree of pollution
    2
    Back to top
    Input data
    Nominal input voltage range
    100 V AC ... 240 V AC
    Input voltage range
    85 V AC ... 264 V AC (< 95 V AC Derating 1 %/V)
    AC frequency range
    50 Hz ... 60 Hz
    Frequency range (f
    N
    )
    50 Hz ... 60 Hz 10 %
    Current consumption
    2.69 A (100 V AC)
    1.08 A (240 V AC)
    Nominal power consumption
    260 VA
    Inrush current
    < 80 A (typical)
    Mains buffering time
    > 10 ms (120 V AC)
    > 10 ms (230 V AC)
    Input fuse
    5 A (slow-blow, internal)
    Recommended breaker for input protection
    6 A ... 16 A (Characteristics B, C, D, K)
    Power factor (cos phi)
    0.99
    Type of protection
    Transient surge protection
    Protective circuit/component
    Varistor
    Back to top
    Output data
    Nominal output voltage
    24 V DC ±1 %
    Setting range of the output voltage (U
    Set
    )
    24 V DC ... 28 V DC ±1 %
    Nominal output current (I
    N
    )
    10 A (-25 °C ... 55 °C)
    Derating
    55 °C ... 70 °C (2.5%/K)
    Connection in parallel
    yes, for redundancy and increased capacity
    Connection in series
    No
    Feedback voltage resistance
    < 35 V DC
    Protection against overvoltage at the output (OVP)
    ≤ 35 V DC
    Control deviation
    change in load, static 10 % ... 90 %
    < 2 % (change in load, dynamic 10 % ... 90 %)
    < 0.1 % (change in input voltage ±10 %)
    Residual ripple
    < 50 mV
    PP
    (with nominal values)
    Output power
    240 W
    Typical response time
    < 1 s
    Maximum power dissipation in no-load condition
    < 1.1 W
    Power loss nominal load max.
    < 18.8 W
    Back to top
    General
    Net weight
    0.66 kg
    Efficiency
    typ. 90 % (120 V AC)
    typ. 93 % (230 V AC)
    MTBF (IEC 61709, SN 29500)
    > 641000 h (40 °C)
    Insulation voltage input/output
    4 kV AC (type test)
    3 kV AC (routine test)
    Degree of protection
    IP20
    Protection class
    I (in closed control cabinet)
    Inflammability class in acc. with UL 94 (housing / terminal blocks)
    V0
    Housing material
    Aluminum / polycarbonate
    Mounting position
    horizontal DIN rail NS 35, EN 60715
    Assembly instructions
    alignable: 0 mm horizontally, 30 mm vertically
    Back to top
    Connection data, input
    Connection method
    Screw connection
    Conductor cross section solid min.
    0.2 mm²
    Conductor cross section solid max.
    2.5 mm²
    Conductor cross section flexible min.
    0.2 mm²
    Conductor cross section flexible max.
    2.5 mm²
    Conductor cross section AWG min.
    24
    Conductor cross section AWG max.
    14
    Stripping length
    8 mm
    Screw thread
    M3
    Back to top
    Connection data, output
    Connection method
    Screw connection
    Conductor cross section solid min.
    0.2 mm²
    Conductor cross section solid max.
    2.5 mm²
    Conductor cross section flexible min.
    0.2 mm²
    Conductor cross section flexible max.
    2.5 mm²
    Conductor cross section AWG min.
    24
    Conductor cross section AWG max.
    14
    Stripping length
    8 mm
    Screw thread
    M3
    Back to top
    Standards
    EMC requirements for noise immunity
    EN 61000-6-1
    EN 61000-6-2
    EMC requirements for noise emission
    EN 61000-6-3
    EN 61000-6-4
    Standard - Safety of transformers
    EN 61558-2-16
    Standard - Electrical safety
    IEC 62368-1 (SELV)
    Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations
    EN 50178/VDE 0160 (PELV)
    Standard – Safety extra-low voltage
    IEC 62368-1 (SELV) und EN 60204-1 (PELV)
    Standard - Safe isolation
    DIN VDE 0100-410
    Standard – Limitation of mains harmonic currents
    EN 61000-3-2
    Mains variation/undervoltage
    EN 61000-4-11
    Back to top
    Conformance/approvals
    UL approvals
    UL/C-UL listed UL 508
    UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
    UL/C-UL Recognized UL 60950-1
    CSA
    CAN/CSA-C22.2 No. 60950-1-07
    CSA-C22.2 No. 107.1-01
    CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
    Back to top
    EMC data
    Electromagnetic compatibility
    Conformance with EMC Directive 2014/30/EU
    Low Voltage Directive
    Conformance with Low Voltage Directive 2014/35/EC
    Electrostatic discharge
    EN 61000-4-2
    Contact discharge
    6 kV (Test Level 3)
    Discharge in air
    8 kV (Test Level 3)
    Electromagnetic HF field
    EN 61000-4-3
    Frequency range
    80 MHz ... 1 GHz
    Test field strength
    10 V/m (Test Level 3)
    Frequency range
    1 GHz ... 2 GHz
    Test field strength
    10 V/m (Test Level 3)
    Frequency range
    2 GHz ... 3 GHz
    Test field strength
    10 V/m (Test Level 3)
    Comments
    Criterion A
    Fast transients (burst)
    EN 61000-4-4
    Input
    4 kV (Test Level 4 - asymmetrical)
    Output
    2 kV (Test Level 3 - asymmetrical)
    Comments
    Criterion B
    Surge voltage load (surge)
    EN 61000-4-5
    Input
    2 kV (Test Level 3 - symmetrical)
    4 kV (Test Level 4 - asymmetrical)
    Output
    1 kV (Test Level 2 - symmetrical)
    2 kV (Test Level 3 - asymmetrical)
    Comments
    Criterion B
    Conducted interference
    EN 61000-4-6
    Frequency range
    0.15 MHz ... 80 MHz
    Voltage
    10 V (Test Level 3)
    Comments
    Criterion A
    Voltage dips
    EN 61000-4-11
    Criterion A
    Normal operating behavior within the specified limits.
    Criterion B
    Temporary impairment to operational behavior that is corrected by the device itself.
    Back to top
    Environmental Product Compliance
    China RoHS
    Environmentally Friendly Use Period = 25;
    For details about hazardous substances go to tab “Downloads”, Category “Manufacturer's declaration”
    Back to top
    Classifications
    ECLASS
    ECLASS 10.0.1
    27040701
    ECLASS 11.0
    27040701
    ECLASS 4.0
    27040700
    ECLASS 4.1
    27040700
    ECLASS 5.0
    27049000
    ECLASS 5.1
    27049000
    ECLASS 6.0
    27049000
    ECLASS 7.0
    27049002
    ECLASS 9.0
    27040701
    Back to top
    ETIM
    ETIM 4.0
    EC000599
    ETIM 6.0
    EC002540
    ETIM 7.0
    EC002540
    Back to top
    UNSPSC
    UNSPSC 13.2
    39121004
    UNSPSC 18.0
    39121004
    UNSPSC 19.0
    39121004
    UNSPSC 20.0
    39121004
    UNSPSC 21.0
    39121004
    Back to to